Technical specification
Insulating cable tray 66 in halogen free
Description
Use
- For support, protection and conduction of cables.
- Insulating material.
- Length: 3m.
- Colour: RAL 7035 Grey.
Installation
- Safe, easy and quick mounting. No burrs or sparks when cutting.
Product composition
- Cable tray system for outdoor/indoor installations. Suitable for humid, saline and chemical environments: U43X(1)
- Insulating supports for outdoor/indoor installations. Suitable for humid, saline and chemical environments: U43X(2)
- Metallic supports for outdoor/indoor installations. Suitable for humid, saline and chemical environments: Stainless steel AISI 304.(2)
- Metallic supports for outdoor/indoor installations. Suitable for humid, saline and chemical environments: Galvanized steel with epoxy coating.(2)
- Metallic supports for dry indoor installations: Sendzimir galvanized steel.
- RoHS Directive compliance II: Compliant.
Quality Marks(3)
GOST R 52868:2007
POCC.RU.C-ES-AK01.H.02882/19
Approvals(3)
Type approval Certificate nº 05116/H0 BV
FZ-123-FZ
Characteristics
BS EN 61537:2007 (IEC 61537:2006) International Cable tray and Cable Ladder standard
|
|
---|---|
Min./max. Service, transport, storage, installation and use temperature
|
-20º C up to +90º C.
|
Protection against mechanical damage
|
20 J at -20ºC (except 60x100: 10 J).
|
Electrical characteristics
|
|
Resistance to flame propagation s/ EN 60695-11-2:2003(4)
|
Non flame propagating system.
|
Coating
|
60x200 mm. : 22,5 Kg/m
|
% perforation in the base area
|
|
Safe Working Load (SWL) acc. Test Type I
|
|
Safe Working Load (SWL) Test conditions
|
|
Glow-wire test acc./ IEC 60695-2-11:2001(4)
|
Severity degree 960ºC.
|
Resistance against humid and saline corrosion
|
Inherently resistant to corrosion. Test is not necessary.
|
EN 50085-2-1:2006 + A1:2011 Cable trunking european standard
|
|
---|---|
Material
|
Non metallic.
|
Minimum storage and transport temperature
|
-45ºC
|
Minimum installation and application temperature
|
-25ºC
|
Maximum application temperature
|
+60ºC
|
Resistance against mechanical impacts during mounting and use
|
Cable tray with cover: 20 J at -25ºC
|
Resistance to flame propagation acc./ IEC 60695-11-2:2003(5)
|
Non-flame propagation.
|
Electrical continuity characteristic
|
Without electrical continuity characteristic.
|
Electrical insulating characteristic
|
With electrical insulating characteristic.
|
Protection degree assured by the enclosure acc./ IEC 60529:1989(5)
|
|
Retention of the system access cover
|
Cover removable only with the aid of a tool.
|
Electrically protective separation
|
With and without internal protective separation.
|
Intended installation positions
|
Surface mounted on the wall.
|
Prevention of contact with liquids
|
Not declared.
|
Assured functions
|
Type 1. (Cable tray profile with cover, separator, cover fixing IK10 and end cover)
|
Rated Voltage(6)
|
750 V.
|
Protection against mechanical damage acc./ IEC 62262:2002(7, 5)
|
Cable tray with cover: Degree IK10.
|
Characteristics
BS EN 61537:2007 (IEC 61537:2006) International Cable tray and Cable Ladder standard
- Insulating Cable tray and support system (except metallic supports)
- Without electrical continuity. Non-conductive system.
- Class B (between 2% and 15%) for perforated cable tray.
- Class A (between 0% and 2%) for non perforated cable tray.
- 60x100 mm. : 10,8 Kg/m
- 60x200 mm. : 22,5 Kg/m
- 60x300 mm. : 33,7 Kg/m
- 100x400 mm. : 77,2 Kg/m
- 100x600 mm. : 116,5 Kg/m
- T = 40 °C span 2 m.
- T = 60 °C span 1,75 m.
- T = 90 °C span 0,5 m.
- Longitudinal deflection lower than 1% and transverse lower than 5%.
- Test Type I : the junction between two lengths of cable tray is placed in the midpoint of the span (the worst situation for testing) so that in a real situation the junction can be placed at any point between two supports.
- The system (cable tray and supports) must be able to support 1,7 times the safe working load (SWL) without collapse.
EN 50085-2-1:2006 + A1:2011 Cable trunking european standard
- IP3X. Continous cable tray with cover.
- IP2X. Perforated cable tray with cover.
Constructive and Functional characteristics
- Outdoor performance: Good performance with exposure to the UVs and to the elements.
- Profile type: Cable trays and covers are made of solid walls and by extrusion.
- Junctions: The junction's thickness is equal or higher than the one of the joined lengths of tray and has longitudinal holes to absorb expansion.
- Insulation: The cable tray is insulating and does not require earthing.
- Supports: Supports must comply with IEC 61537:2006 and shall resist at least the maximum loads of the carried cable trays.
- Product packaging: Product properly packaged and clearly identified.
Compulsory regulations
Conformity with the demands of European Directive 2014/35/EU
|
|
---|---|
CE Marking(8)
|
Conformity with standard EN 61537:2007.
|
Compulsory regulations
Conformity with the demands of European Directive 2014/35/EU
Characteristics of steel coated with epoxy resin raw material
- Base raw material: Steel
- Coating: Highly corrosion resistant coating + Epoxy/polyester resin
- Classification: Steels DD11 acc./EN 10111:2008 and DC01 acc./UNE-EN 10130:2008
Characteristics of stainless steel coated with epoxy resin raw material
- Base raw material: Stainless steel
- Coating: Epoxy / Polyester resin
- Classification:
EN 10088: 1.4301
AISI:AISI 304
NF A35-586:Z6CN 18-09
DIN 17440:1.4301(V2A)
BS:304,S31
Characteristics of sendzimir steel raw material
- Base raw material: Steel
- coating according to UNE-EN 10130:2008: Pre-galvanized steel Z275-MBO
- Classification acc./UNE-EN 10346: 2015: DX53D+Z275-MBO
Characteristics of stainless steel AISI 316 material
- Base raw material: Stainless steel A4
- Behaviour to chemicals exposure:
Resistant to the most common:
- Oils (mineral and vegetable)
- Acetones
- Acids
- Alcohols
- Ammoniac
- Aliphatic carbon hydrides
- Hydroxides
- Carbonates
- Phosphates
- Nitrates
- Sulphates (9) - Classification:
EN 10088-1: 1.4401
AISI: AISI 316
NF A35-573: Z7 CND 17.11.02
DIN 17440: 1.4401(V4A)
BS: 316 S 31
EN ISO 3506-4 A4
Notes
1. For aggressive chemical environments (concentrated acids ans hydroxides) we strongly recommend, if possible, the use of the product in U23X.
2. In outdoor installations or in aggressive chemical environments it is necessary to periodically check the installation. In outdoor installations, a colour change may occur on the raw material, without affecting its mechanical features. If painted, dark colored paints might cause further warming of the product once exposed to the sun.
3. Except for new part numbers, which are under process of obtaining quality marks and approvals. See updated information of each part number on www.unex.net
4. Tested according to standard prescriptions of EN 61537:2007 . Equivalent to IEC 61537:2006 Cable tray and cable ladder standard.
5. Tested according to standard prescriptions of EN 50085-1
6. Test carried out considering the use of the cable tray with cover to provide additional insulation to an isolated conductor according to requirements of EN 50085-1 standard (Low Voltage Directive)
7. Mounted with Cover fixing Ref. 66845-44 or 66855-44. Without this device: Impact resistance 2J and Protection against mechanical damages Grade IK07.
8. The values indicated according to IEC 61537:2006 have been tested under its European implementation EN 61537:2007.
9. All features marked are based on random tests of the material in the manufacture of our products. However, they only reflect the values accepted by the raw material manufacturers, which are provided only as information and guidance.