Raw material
|
|
|---|---|
|
Trunkings
|
Aluminium (See technical data for raw material).
|
|
Fittings and accessories
|
U24X (See technical data for raw material).
|
|
Applications
|
|
|---|---|
|
Applications
|
Indoor installations.
|
|
Silicone contents
|
|
|---|---|
|
Silicone free
|
<0,01%
|
|
Directive 2011/65/EU
|
|
|---|---|
|
RoHS II Compliant
|
Compliant.
|
|
EN 50085-2-1:2006 + A1:2011
|
|
|---|---|
|
Minimum storage and transport temperature
|
-45ºC
|
|
Minimum installation and application temperature
|
-5ºC
|
|
Maximum application temperature
|
+60ºC
|
|
Resistance against mechanical impacts during mounting and use
|
|
|
Resistance to flame propagation
|
Non-flame propagation.
|
|
Electrical continuity characteristic
|
With electrical continuity characteristic.
|
|
Electrical insulating characteristic
|
Without electrical insulating characteristic.
|
|
Protection degree assured by the enclosure
|
|
|
Retention of the system access cover
|
Cover removable only with the aid of a tool.
|
|
Electrically protective separation
|
With internal protective separation.
|
|
Intended installation positions
|
|
|
Prevention of contact with liquids
|
Relying on manufacturer's instructions allowing all installation positions of the CTS and all positions of insulated conductors and live parts in CTS.
|
|
Type
|
Type 3.
|
|
Rated Voltage
|
750 V
|
|
Linear impedance
|
2,82 10-8 Ohm/m
|
|
Protection against mechanical damage
|
IK07
|
|
Fixing for apparatus mounting of socket outlets
|
Resistance to extraction of 81 N
|
|
EN 60695-2-11:2001
|
|
|---|---|
|
Glow-wire test
|
Severity degree: 960ºC.
|
|
European Directive 2014/35/EU
|
|
|---|---|
|
CE Marking
|
Conformity with standard EN 50085-2-1:2006+A1:2011.
|
1. Except for new part numbers, which are under process of obtaining quality marks and approvals. See updated information of each part number on www.unex.net
2. All features marked are based on random tests of the material in the manufacture of our products. However, they only reflect the values accepted by the raw material manufacturers, which are provided only as information and guidance.
3. Detection limit for the analytical technique applied.