EN 50085-2-1:2006 + A1:2011
Licence nº: NF004_1181
EN 50085-2-1:2006 + A1:2011
Licence nº: 101832
UL 1565.
CSA C22.2 No. 18.5.
Suitable for temperatures not exceeding 50ºC.
File nº: E 75725 (M)
Rules for the Classification of Steel Ships
Type Approval Certificate nº 05116/I0 BV
NI 52.40.02
Licence: Annex attachment of suppliers.
Trunkings: 30x40, 40x60, 60x90 and 60x110 mm
Raw material
|
|
---|---|
Trunkings
|
U23X. (See technical data for raw material).
|
Fittings and accessories
|
U24X. (See technical data for raw material).
|
Applications
|
|
---|---|
Applications(3)
|
Trunking system for indoor-outdoor installations.
|
Silicone contents
|
|
---|---|
Silicone free
|
<0,01%
|
Directive 2011/65/EU
|
|
---|---|
RoHS II Compliant
|
Compliant.
|
EN 50085-2-1:2006 + A1:2011
|
|
---|---|
Minimum storage and transport temperature
|
-45ºC
|
Minimum installation and application temperature
|
-25ºC
|
Maximum application temperature
|
+60ºC
|
Resistance against mechanical impacts during mounting and use
|
|
Resistance to flame propagation
|
Non-flame propagation.
|
Electrical continuity characteristic
|
Without electrical continuity characteristic.
|
Electrical insulating characteristic
|
With electrical insulating characteristic.
|
Protection degree assured by the enclosure
|
|
Retention of the system access cover
|
Cover removable only with the aid of a tool.
|
Electrically protective separation
|
With and without internal protective separation.
|
Intended installation positions
|
|
Prevention of contact with liquids
|
Not declared.
|
Type
|
Type 2.
|
Rated Voltage
|
750 V
|
Protection against mechanical damage(4)
|
IK08/IK10
|
EN 60695-2-11:2001
|
|
---|---|
Glow-wire test
|
Severity degree: 960ºC.
|
European Directive 2014/35/EU
|
|
---|---|
CE Marking
|
Conformity with standard EN 50085-2-1:2006+A1:2011.
|
Electrical Equipment (Safety) Regulations 2016
|
|
---|---|
UKCA Marking
|
Conformity with standard EN 50085-2-1:2006+A1:2011.
|
1. Except for new part numbers, which are under process of obtaining quality marks and approvals. See updated information of each part number on www.unex.net
2. Approved for the intended installation positions: Semi flush or surface mounted on the wall or ceiling.
3. In outdoor installations or in aggressive chemical environments it is necessary to periodically check the installation. In outdoor installations, a colour change may occur on the raw material, without affecting its mechanical features. In order to absorb expansions caused by temperature changes in outdoor installations, we recommend using metal fixings each 0,5m, leaving 1cm separation between covers and placing end covers at the ends of vertical routings. If painted, paints might cause further warming of the product once exposed to the sun, in such a case we recommend to install Trunking 73 in U43X.
4. The profile system with finishing elements is certified by LCIE and VDE as IK08 type 2. The profiles are also certified as IK10 type 1
5. All features marked are based on random tests of the material in the manufacture of our products. However, they only reflect the values accepted by the raw material manufacturers, which are provided only as information and guidance.
6. Detection limit for the analytical technique applied.