EN 50085-2-1:2006 + A1:2011
Licence nº: NF004_1178
Rules for the Classification of Steel Ships
Type Approval Certificate nº 05116/I0 BV
Raw material
|
|
---|---|
Trunkings
|
U43X. (See technical data for raw material).
|
Fittings and accessories
|
U42X. (See technical data for raw material).
|
Applications
|
|
---|---|
Applications(2)
|
Indoor and outdoor installation.
|
Silicone contents
|
|
---|---|
Silicone free
|
<0,01%
|
Directive 2011/65/EU
|
|
---|---|
RoHS II Compliant
|
Conformity.
|
EN 50085-2-1:2006 + A1:2011
|
|
---|---|
Minimum storage and transport temperature
|
-45ºC
|
Minimum installation and application temperature
|
-25ºC
|
Maximum application temperature
|
+90ºC
|
Resistance against mechanical impacts during mounting and use
|
|
Resistance to flame propagation
|
Non-flame propagation.
|
Electrical continuity characteristic
|
Without electrical continuity characteristic.
|
Electrical insulating characteristic
|
With electrical insulating characteristic.
|
Protection degree assured by the enclosure
|
IP4X. Mounted on the wall or ceiling.
|
Retention of the system access cover
|
Cover removable only with the aid of a tool.
|
Electrically protective separation
|
With internal protective separation.
|
Intended installation positions
|
Semi flush or surface mounted on the wall or ceiling.
|
Prevention of contact with liquids
|
Not declared.
|
Type
|
Type 2. Type 3.
|
Rated Voltage
|
750 V
|
Protection against mechanical damage
|
IK07
|
Fixing for apparatus mounting of socket outlets
|
Resistance to extraction of 81 N
|
EN 60695-2-11:2001
|
|
---|---|
Glow-wire test
|
Severity degree: 960ºC.
|
Electrical Equipment (Safety) Regulations 2016
|
|
---|---|
UKCA Marking
|
Conformity with standard EN 50085-2-1:2006+A1:2011.
|
European Directive 2014/35/EU
|
|
---|---|
CE Marking
|
Conformity with standard EN 50085-2-1:2006+A1:2011.
|
1. Except for new part numbers, which are under process of obtaining quality marks and approvals. See updated information of each part number on www.unex.net
2. In outdoor installations or in aggressive chemical environments it is necessary to periodically check the installation. In outdoor installations, a colour change may occur on the raw material, without affecting its mechanical features. In order to absorb expansions caused by temperature changes in outdoor installations, we recommend using metal fixings each 0,5m, leaving 1cm separation between covers and placing end covers at the ends of vertical routings.
3. Value corresponding to the last 5 years, subject to availability.
4. Detection limit for the analytical technique applied.
5. All features marked are based on random tests of the material in the manufacture of our products. However, they only reflect the values accepted by the raw material manufacturers, which are provided only as information and guidance.