Raw material
|
|
---|---|
Trunkings
|
U23X. (See technical data for raw material).
|
Fittings and accessories
|
U24X. (See technical data for raw material).
|
Applications
|
|
---|---|
Applications(2)
|
Trunking system for indoor-outdoor installations.
|
Silicone contents
|
|
---|---|
Silicone free
|
<0,01%
|
Directive 2011/65/EU
|
|
---|---|
RoHS II Compliant
|
Compliant.
|
EN 50085-2-1:2006 + A1:2011
|
|
---|---|
Minimum storage and transport temperature
|
-45ºC
|
Minimum installation and application temperature
|
-25ºC
|
Maximum application temperature
|
+60ºC
|
Resistance against mechanical impacts during mounting and use
|
|
Resistance to flame propagation
|
Non-flame propagation.
|
Electrical continuity characteristic
|
Without electrical continuity characteristic.
|
Electrical insulating characteristic
|
With electrical insulating characteristic.
|
Protection degree assured by the enclosure
|
IP3X
|
Retention of the system access cover
|
Cover removable only with the aid of a tool.
|
Electrically protective separation
|
Without internal protective separation.
|
Intended installation positions
|
Semi flush or surface mounted on the wall or ceiling.
|
Prevention of contact with liquids
|
Not declared.
|
Type
|
Type 1.
|
Rated Voltage
|
750 V
|
Protection against mechanical damage
|
IK08
|
EN 60695-2-11:2001
|
|
---|---|
Glow-wire test
|
Severity degree: 960ºC.
|
European Directive 2014/35/EU
|
|
---|---|
CE Marking
|
Conformity with standard EN 50085-2-1:2006+A1:2011.
|
Electrical Equipment (Safety) Regulations 2016
|
|
---|---|
UKCA Marking
|
Conformity with standard EN 50085-2-1:2006+A1:2011.
|
1. Except for new part numbers, which are under process of obtaining quality marks and approvals. See updated information of each part number on www.unex.net
2. In outdoor installations or in aggressive chemical environments it is necessary to periodically check the installation. In outdoor installations, a colour change may occur on the raw material, without affecting its mechanical features. In order to absorb expansions caused by temperature changes in outdoor installations, we recommend using metal fixings each 0,5m, leaving 1cm separation between covers and placing end covers at the ends of vertical routings. If painted, paints might cause further warming of the product once exposed to the sun, in such a case we recommend to install Trunking 73 in U43X.
3. All features marked are based on random tests of the material in the manufacture of our products. However, they only reflect the values accepted by the raw material manufacturers, which are provided only as information and guidance.
4. Detection limit for the analytical technique applied.