Raw material
|
|
---|---|
Trunkings
|
U23X. (See technical data for raw material).
|
Fittings and accessories
|
U24X. (See technical data for raw material).
|
Applications
|
|
---|---|
Applications(2)
|
Trunking system for indoor-outdoor installations.
|
Silicone contents
|
|
---|---|
Silicone free
|
<0,01%
|
Directive 2011/65/EU
|
|
---|---|
RoHS II Compliant
|
Compliant.
|
EN 50085-2-1:2006 + A1:2011 European cable trunking standard
|
|
---|---|
Products affected
|
Covers, strip bases detachable strips and finishing elements.
|
Minimum storage and transport temperature
|
-45ºC
|
Minimum installation and application temperature
|
-25ºC
|
Maximum application temperature
|
+60ºC
|
Resistance against mechanical impacts during mounting and use
|
|
Resistance to flame propagation
|
Non-flame propagation.
|
Electrical continuity characteristic
|
Without electrical continuity characteristic.
|
Electrical insulating characteristic
|
With electrical insulating characteristic.
|
Protection degree assured by the enclosure
|
IP3X.
|
Retention of the system access cover
|
Cover removable only with the aid of a tool.
|
Electrically protective separation
|
Without internal protective separation.
|
Intended installation positions
|
Semi flush or surface mounted on the wall or ceiling.
|
Prevention of contact with liquids
|
Not declared.
|
Type
|
Type 2.
|
Rated Voltage
|
750 V
|
Protection against mechanical damage
|
|
EN 62275: 2015 European cable tie standard
|
|
---|---|
Products affected
|
Single base plates.
|
Material
|
Non metallic.
|
Mechanical resistance of fixing elements
|
Type 2.
|
Minimum - maximum service temperature
|
-40ºC / +50ºC
|
Minimum installation temperature
|
-15ºC
|
Resistance to flamme propagation
|
Non-flame propagation.
|
Resistance to the UVs
|
Not declared.
|
Resistance to corrosion (humid and saline)
|
Not declared.
|
Static load
|
100 N
|
EN 61386-25:2011 European conduit fixing device standard
|
|
---|---|
Products affected
|
Cable clamps.
|
Resistance to lateral load
|
Heavy.
|
Resistance to axial load
|
None declared.
|
Resistance to impact
|
Light.
|
Lower temperature range. Transport, application and installation
|
-25ºC
|
Upper temperature range. Application and installation
|
+60ºC
|
Resistance to flame propagation
|
Non-flame propagating.
|
EN 60695-2-11:2001
|
|
---|---|
Glow-wire test
|
Severity degree: 960ºC.
|
European Directive 2014/35/EU
|
|
---|---|
CE Marking
|
Conformity with standard EN 50085-2-1:2006+A1:2011.
|
1. Except for new part numbers, which are under process of obtaining quality marks and approvals. See updated information of each part number on www.unex.net
2. In outdoor installations or in aggressive chemical environments it is necessary to periodically check the installation. In outdoor assemblies we recommend assembling a continuous base and an angled cable bushing bolted to the wall in the lower part of the trunking in a vertical pathway.
3. Detection limit for the analytical technique applied.