EN 61537: 2007
Licence nº: 030/001911
EN 50085-1:2006
EN 50085-1:2006/A1:2013
EN 50085-2-1:2008
EN 50085-2-1:2008/A1:2012
Licence nº: 030/002491
EN 61537: 2007
Licence nº: 670639/M2
EN 61537: 2007
Licence nº: 40011889
ANSI / UL 568: 2009 -
CAN/CSA C22.2 No. 126.2-02
Licence nº: E335136
Type approval Certificate nº 05116/H0 BV
BS EN 61537:2007 (IEC 61537:2006) International Cable tray and Cable Ladder standard
|
|
---|---|
Min./max. Service, transport, storage, installation and use temperature
|
-20º C up to +60º C.
|
Protection against mechanical damage
|
20 J at -20ºC (except 60x100: 10 J and 60x75: 5 J).
|
Electrical characteristics
|
|
Resistance to flame propagation acc./ EN 60695-11-2:2003(6)
|
Non flame propagating system.
|
Coating
|
Without coating (except metallic supports with metallic coating and metallic supports with organic coating).
|
% perforation in the base area
|
|
Safe Working Load (SWL) acc. Test Type I
|
|
Safe Working Load (SWL) Test conditions
|
|
Glow-wire test acc./ IEC 60695-2-11:2001(6)
|
Severity degree 960ºC.
|
Resistance against humid and saline corrosion
|
Inherently resistant to corrosion. Test is not necessary.
|
DIN 8061 and ISO/TR 10358
|
|
---|---|
Performance against chemical ambiances
|
Chemical resistance against different substances defined by the standard depending on the concentration and temperature.
|
EN 50085-2-1:2006 + A1:2011 Cable trunking european standard
|
|
---|---|
Material
|
Non metallic.
|
Minimum storage and transport temperature
|
-45ºC
|
Minimum installation and application temperature
|
-25ºC
|
Maximum installation and application temperature
|
+60ºC
|
Resistance against mechanical impacts during mounting and use
|
Cable tray with cover: 20 J at -25ºC
|
Resistance to flame propagation acc./ IEC 60695-11-2:2003(7)
|
Non-flame propagation.
|
Electrical continuity characteristic
|
No electrical continuity.
|
Electrical insulating characteristic
|
Electrically insulating.
|
Protection degree assured by the enclosure acc./ IEC 60529:1989(7)
|
|
Retention of the system access cover
|
Cover removable only with the aid of a tool.
|
Electrically protective separation
|
With and without internal protective separation.
|
Intended installation positions
|
Surface mounting on the wall.
|
Prevention of contact with liquids
|
Not applicable.
|
Assured functions
|
Type 1. (Cable tray profile with cover, separator, cover fixing IK10 and end cover)
|
Rated Voltage(8)
|
750 V.
|
Protection against mechanical damage acc./ IEC 62262:2002(9, 7)
|
Cable tray with cover: Degree IK10.
|
1. In outdoor installations or in aggressive chemical environments it is necessary to periodically check the installation.
2. In outdoor installations, a colour change may occur on the raw material, without affecting its mechanical features. If painted, dark colored paints might cause further warming of the product once exposed to the sun, in such case we recommend to install Cable trays in U48X.
3. Detection limit for the analytical technique applied.
4. Except for new part numbers, which are under process of obtaining quality marks and approvals. See updated information of each part number on www.unex.net
5. The values indicated according to IEC 61537:2006 have been tested under its European implementation EN 61537:2007.
6. Tested according to standard prescriptions of EN 61537:2007 . Equivalent to IEC 61537:2006 Cable tray and cable ladder standard.
7. Tested according to standard prescriptions of EN 50085-1
8. Test carried out considering the use of the cable tray with cover to provide additional insulation to an isolated conductor according to requirements of EN 50085-1 standard (Low Voltage Directive)
9. Mounted with Cover fixing Ref. 66845 or 66855. Without this device: Impact resistance 5J and Protection against mechanical damages Grade IK08.
10. All features marked are based on random tests of the material in the manufacture of our products. However, they only reflect the values accepted by the raw material manufacturers, which are provided only as information and guidance.