EN 61537:2007 European Cable tray and Cable Ladder standard
Licence nº: 030/002558
EN 61537: 2007
Licence nº: 40054087
EN 61914: 2016 European Standard for cable cleats
Cable cleats in U48X. Licence nº: 40048000
ANSI / UL 568: 2009 -
CAN/CSA C22.2 No. 126.2-02
Licence nº: E335136
BS EN 61537:2007 (IEC 61537:2006) International Cable tray and Cable Ladder standard
|
|
---|---|
Min./max. transport, storage, installation and application temperature
|
-20 ºC up to +60 ºC.
|
Impact resistance(7)
|
20 J at -20 ºC
|
Electrical characteristics
|
|
Resistance to flame propagation acc./ EN 60695-11-2:2003(8)
|
Non flame propagating system.
|
Coating
|
|
% Perforation of the base area of cable ladder
|
Class Y (more than 80% up to 90%)
|
Available dimensions
H:85 mm |
|
Available dimensions
H:135 mm |
|
Safe Working Load (SWL) acc. Test Type I
|
|
Safe Working Load (SWL) Test conditions
|
|
Glow-wire test acc./ IEC 60695-2-11:2001(8)
|
Severity degree 960ºC.
|
Performance against corrosion (humid and saline)
|
Inherently resistant to corrosion and therefore do not require testing.
|
DIN 8061 and ISO/TR 10358
|
|
---|---|
Performance against chemical ambiances
|
Chemical resistance against different substances defined by the standard depending on the concentration and temperature.
|
EN 61914:2016 (IEC 61914:2015) International Cable Cleat standard
|
|
---|---|
Material(6)
|
Non metallic
|
Minimum and Maximum temperature for permanent application
|
-25 ºC up to +60 ºC
|
Impact resistance
|
|
Resistance to electromechanical forces
|
Not declared
|
Maximum lateral and axial load
|
|
Resistance to the UV light
|
Resistant
|
Resistance to corrosion (humid and saline)
|
Inherently resistant. No testing required.
|
Conformity with the demands of European Directive 2014/35/EU
|
|
---|---|
CE Marking(8)
|
|
CE Marking(6)
|
|
1. In outdoor installations or in aggressive chemical environments it is necessary to periodically check the installation.
2. Some parts are made in U48X. For more details, see the Part number’s chart.
3. Detection limit for the analytical technique applied.
4. Except for new part numbers, which are under process of obtaining quality marks and approvals. See updated information of each part number on www.unex.net
5. The values indicated according to IEC 61537:2006 have been tested under its European implementation EN 61537:2007.
6. Tested according to standard prescriptions of EN 61914:2016 . Equivalent to IEC 61914:2015 Cable cleat standard.
7. -50ºC/-70ºC (20 J H:135 mm, 10 J H: 85 mm)
8. Tested according to standard prescriptions of EN 61537:2007 . Equivalent to IEC 61537:2006 Cable tray and cable ladder standard.
9. All features marked are based on random tests of the material in the manufacture of our products. However, they only reflect the values accepted by the raw material manufacturers, which are provided only as information and guidance.
10. Excepting references 67812-48 and 67822-48.
11. Value corresponding to the last 5 years, subject to availability.
12. For aggressive chemical environments (concentrated acids ans hydroxides) we strongly recommend, if possible, the use of the product in U23X.