ГOCT P 61084-1:2007 (GOST R 61084-1:2007)
POCC ES.AM05.H09265
Raw material
|
|
---|---|
Watertight lid
|
Stainless steel
|
Floor box
|
U24X (See technical data for raw material).
|
Applications
|
|
---|---|
Applications
|
Indoor installations.
|
Silicone contents
|
|
---|---|
Silicone free
|
<0,01%
|
Directive 2011/65/EU
|
|
---|---|
RoHS II Compliant
|
Compliant.
|
EN 50085-2-2:2008
|
|
---|---|
Minimum storage and transport temperature
|
-45ºC
|
Minimum installation and application temperature
|
-5ºC
|
Maximum application temperature
|
+60ºC
|
Resistance to flame propagation
|
Non-flame propagation.
|
Electrical continuity characteristic
|
Without electrical continuity characteristic.
|
Electrical insulating characteristic
|
With electrical insulating characteristic.
|
Protection degree assured by the enclosure
|
IP4X.
|
Retention of the system access cover
|
Cover removable only with the aid of a tool.
|
Resistance against mechanical impacts during mounting and use
|
2 J at -5ºC
|
Electrically protective separation
|
With internal protective separation.
|
According to floor treatment
|
Floor box for wet-treatment of floor
|
According to resistance to vertical load applied through small surface area
|
2.500 N
|
According to resistance to vertical load applied through large surface area
|
5.000 N
|
Intended installation positions
|
Flushed in the pavement.
|
Rated Voltage
|
750 V
|
Protection against mechanical damage
|
IK07
|
EN 60695-2-11:2001
|
|
---|---|
Glow-wire test
|
Severity degree: 960ºC
|
European Directive 2014/35/EU
|
|
---|---|
CE Marking
|
Conformity with standard EN 50085-2-2:2008.
|
1. Except for new part numbers, which are under process of obtaining quality marks and approvals. See updated information of each part number on www.unex.net
2. Detection limit for the analytical technique applied.